      Outdoor prefabricated substation (European)

      YB-12 / 0.4 - Outdoor prefabricated substation (European) is widely used in urban power grid transformation, residential quarters, high-rise buildings, industries and mines, hotels, shopping malls, airports, railways, oil fields, docks, highways, temporary power facilities and other indoor and outdoor places.

      products detial


      What we can do ? different country different requirement all we can offer.

      Mid-voltage ( kV)

      3.6~35kv

      (E.g. 35,33,24,22,20,18,15.75,13.8,13.2,12,11,10.5,10,7.2,6.6,6.3,6 etc.)

      To Low voltage ( V)

      100-660V

       (E.g. 100,110,115,120,127,208,200,220,230,240,346,380,400,410,415,440,480,660 etc.)

      Frequency (HZ)

      50Hz or 60Hz

      YB-12 / 0.4 - Outdoor prefabricated substation (European)


      1、 Overview

      It is widely used in urban power grid transformation, residential quarters, high-rise buildings, industries and mines, hotels, shopping malls, airports, railways, oil fields, docks, highways, temporary power facilities and other indoor and outdoor places.

      2、 Model and description

      YB□-12/0.4-□

      □ - transformer capacity

      12 / 0.4 - rated voltage (HV / LV)

      □-design serial number

      YB intelligent integrated substation

      3、 Use environment

      The altitude shall not exceed 100om; Ambient temperature: - 25 ℃ ~ + 40 ℃;

      ◆ relative humidity: the daily average value shall not be greater than 95%, and the monthly average value shall not be greater than 90%;

      ◆ installation site; In places without fire, explosion hazard, conductive dust, chemical corrosive gas and violent vibration, if the above conditions are exceeded, the user can negotiate with our company.

      4、 Functions and features

      ◆ high voltage switchgear, transformer and low voltage switchgear are Trinity, with strong completeness; ◆ perfect high and low voltage protection, safe and reliable operation and simple maintenance;

      Less land occupation, less investment, short production cycle and convenient movement; ◆ flexible and diverse wiring schemes;

      Unique structure: unique honeycomb structure, double-layer (composite plate) shell is firm, heat insulation, heat dissipation and ventilation, beautiful and high protection grade. The shell materials are stainless steel qin alloy, aluminum alloy, cold-rolled plate and color steel plate; ◆ various types: universal, villa, compact and other styles;

      ◆ the high-voltage ring network cabinet can be equipped with network automation terminal (FTU) to realize reliable detection of short circuit and single-phase grounding fault. It has the "four remote" function to facilitate the upgrading of distribution network automation.

      5、 Technical parameters of load switch

      No.

      Name

      Unit

      FN12-12 load switch

      FZM12-12 Vacuum load switch

      1

      Rated voltage

      kV

      10

      2

      Maximum operating voltage

      kV

      12

      3

      Rated frequency

      Hz

      50

      4

      Rated current

      630

      5

      Rated open load-off current

      A

      6

      Heat-stable current (effective value)

      kA/S

      20/2

      20/4

      7

      Dynamic current

      kA

      50

      50

      8

      Short-circuit turn-off current (peak)

      kA

      50

      50

      9

      Number of breaks at full load

      time

      20

      10000

      10

      Mechanical life

      time

      2000

      10000

      11

      1min Working frequency pressure resistance(Alternatively and to the ground)

      kV

      42

      42

      12

      Lightning impact voltage(Interphase and ground)

      kV

      75

      75

      VI. Technical parameters of the high-voltage fuse

      No.

       Rated voltage (KV)

       drop-out current (A)

       drop-out current (KA)

      Rated current of melt(A)

      British model

      Domestic model


      SDL※J


      12

      40

      31.5

      6.3,10,16.20,25,31.5,40

      SFL※J

      XRNT-12

      12

      100

      31.5

      5o,63,71,80,100

      SKL※J


      12

      125

      31.5

      125

      * Note: N, determined by whether to install the impactor, is collision needle and A is needle.

      No.

      Defastener form

      Stripper rated current A

      Fault ability KA(AC380V)

      DW15-630

      Thermal-electromagnetic

       or electronic type

      315,400,630

      40

      Dw15-1000

      630,800,1000

      50

      DW15-1600

      1600

      50

      Dw15-2500

      1600,2000,2500

      60

      cw1-2000

      Intelligent

      630,800,1000,1250,1600,2000

      65(80)

      cw1-3200

      2000,2500,3200

      100

      Note: (80) is high molecular fracture.

      copy (2) - 800


      ×
      Add WeChat friends

      Click to copy the WeChat ID

      WeChat ID:+86 180-7778-0057

      Copy successfully
      WeChat ID:+86 180-7778-0057
      Add WeChat friends
      Go to WeChat to add friends

      WhatsApp

      Tel

      0771-3860772
      7*24 Service Hotline

      ?

      WeChat

      二維碼Scan to add WeChat
      TOP
      亚洲 自拍 另类 欧美 综合_蜜桃成人无码区免费视频网站_丝袜偷拍欧美主播另类_亚洲国产精品第一区二区三区

        <form id="fvlnd"></form>
        <form id="fvlnd"><th id="fvlnd"><th id="fvlnd"></th></th></form>

          <sub id="fvlnd"><listing id="fvlnd"><menuitem id="fvlnd"></menuitem></listing></sub>
          <listing id="fvlnd"><listing id="fvlnd"><meter id="fvlnd"></meter></listing></listing>